无互连线逆变器并联系统均流分析
作者:刘俊华 竺兴妹 上传时间:2007/12/11 14:46:23
摘要: 理论分析了无互连线逆变器并联系统中等效输出阻抗Z∠θ不一致时的功率分布情况。分析表明,Z∠θ呈感性时,Z∠θ不一致会引起无功功率偏差;而Z∠θ呈阻性时,Z∠θ不一致会导致有功功率偏差。在此基础上提出了下垂系数调整法以减小功率偏差。仿真和实验结果都表明提出的方法可明显提高各逆变模块的功率均分精度。
叙词:逆变器;并联;无功功率;有功功率
Abstract:In the parallel inverters without control interconnection,the power distribution is analysed when the equivalent output impendance Z is different between paralleled inverters. Theory analyse indicates that when Z is inductive,the unbalance of Z leads to reactive powers differencewhile Z is resistiveactive power can not be shared because of the unbalance of Z.Based on this analyse,the method called droop coefficient regulation is presented in order to reduce power error. Simulation and experiment prove that the way can improve power-sharing precision markedly.
Keyword:Inverter; parallel; reactive power; active power
说明:本站会员正确输入用户名和密码进行登录系统后才能查看文章详细内容和参与评论。
--本文摘自《电源世界》,已被阅读9593次
免责声明:本文仅代表作者个人观点,与电源在线网无关。其原创性以及文中陈述文字和内容未经本站证实,对本文以及其中全部或者部分内容、文字的真实性、完整性、及时性本站不作任何保证或承诺,请读者仅作参考,并请自行核实相关内容。
投稿热线 :0755-82905460 邮箱 :news@cps800.com
关于本文的网友评论:
本文暂时还没有网友发表评论信息!